Weight |
69 kg |
Motor size |
150 |
Size |
990 mm |
Rotor surface |
Painted black |
Electronics housing material |
Die-cast aluminum, painted black |
Blade material |
Sheet aluminum insert, sprayed with PP plastic |
Fan housing material |
Sheet steel, galvanized and coated with black plastic (RAL 9005) |
Guard grille material |
Steel, coated with black plastic (RAL 9005) |
Number of blades |
5 |
Blade pitch |
0° |
Airflow direction |
V |
Direction of rotation |
Clockwise, viewed toward rotor |
Degree of protection |
IP44 |
Insulation class |
"F" |
Ambient temperature note |
Occasional start-up at temperatures between -40°C and -25°C is permitted. For continuous operation at ambient temperatures below -25°C (such as refrigeration applications), use must be made of a fan design with special low-temperature bearings. |
Moisture (F) / Environmental (H) protection class |
H2 |
Max. permitted ambient temp. for motor (transport/storage) |
+80 °C |
Min. permitted ambient temp. for motor (transport/storage) |
-40 / -55 °C |
Installation position |
Shaft horizontal with cable exit ±45° or rotor at bottom; rotor at top not permissible |
Condensation drainage holes |
On rotor side |
Mode |
S1 |
Motor bearing |
Ball bearing |
Technical features |
- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Operation and alarm display
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (parameter setting)
- External release input
- Alarm relay
- Integrated PID controller
- Motor current limitation
- PFC, passive
- RS-485 MODBUS-RTU
- Soft start
- Control input 0-10 VDC / PWM
- Temperature derating
- Thermal overload protection for electronics/motor
- Line undervoltage / phase failure detection |
EMC immunity to interference |
According to EN 61000-6-2 (industrial environment) |
EMC interference emission |
According to EN 61000-6-4 (industrial environment) |
Touch current according to IEC 60990 (measuring circuit Fig. 4, TN system) |
<= 3,5 mA |
Electrical hookup |
Terminal box |
Motor protection |
Reverse polarity and locked-rotor protection |
Protection class |
I (with customer connection of protective earth) |
Conformity with standards |
EN 14986; EN 60079-0; EN 60079-1; EN 60079-7; EN 60079-11; EN 61800-5-1 / CE |
Approval |
EAC / II 2G |